Products
Purchase Specification



PURCHASE SPECIFICATION

POWER QUALITY FILTER
with Total Surge Cancellation, Wide Voltage Range,
High Endurance and Noise Filtration

(120 VOLT, 60 HERTZ, SINGLE PHASE, 15, 20 and 30  AMPERE)

CORD-CONNECTED- MODE 1

 

INTRODUCTION: This is a purchase specification outline for high performance, 1,000 surge endurance power line filtering with Wide Voltage Range, Total Surge Cancellation (WVR-TSC) and noise filtration performance.

Description

Rating

NOTES

Nominal Input Voltage

120 VAC, 50-60Hz

NEC power Standards

MCOV (Maximum Continuous Operating Voltage)

175 VAC

 

Usable Voltage Range:

Wide Voltage Range (WVR) technology.

 

85-175 VAC

Fully dynamic performance with no fixed voltage clamping components offering superior performance when used with generators and in brown-out conditions

Input current rating

15,  20 or 30 Amps

Model dependent

Overload protection

 

Thermal circuit breakers where applicable

Noise, Suppression circuits

Series connected transformer in “hot” leg, followed by dynamic filtering.

Surge voltage totally canceled for optimum protection.

Mode of Operation:

(Avoid mode 2 and all-mode products to avoid system noise and reliability problems)

Mode 1 (Line-Neutral)

This mode protects L-N while avoiding system noise and product degradation associated with  ground system contamination.

Endurance (ANSI C62.41 Standard surge)

1,000 surges- 6,000 Volt 3,000 Amp endurance rating

Filter technology does not degrade with use.

No sacrificial components.

EMI/RFI Filtering

20 dB rejection at 100 kHz.

 

Surge Voltage Let-Through* (ANSI 6,000V, 3,000A surge)

Less than 20 Volts peak.

The cancellation circuit effectively eliminates any surge damage potential.

Safety Agency Approvals

CSA 22.2 No. 8-M1986, UL 1283 5th edition, UL 1363

US and Canada Safety Certified.

Packaging

Heavy gauge steel cabinet

 

Outlets

2-10

Model dependent

Power cord, plug

6 ft nominal

Model dependent

Dimensions

 

Model dependent

Weight

 7 lb. to 15 lb.

Model dependent

Warranty

10 years

 


*Surge Voltage Let-Through is the peak voltage that exceeds the powerline peak voltage.