PURCHASE SPECIFICATION
POWER QUALITY FILTER
with Total Surge Cancellation, Wide Voltage Range,
High Endurance and Noise Filtration
(120 VOLT, 60 HERTZ, SINGLE PHASE, 15, 20 and 30 AMPERE)
CORD-CONNECTED- MODE 1

|
 |
INTRODUCTION: This is a purchase specification outline for high performance, 1,000 surge endurance power line filtering with Wide Voltage Range, Total Surge Cancellation (WVR-TSC) and noise filtration performance.
|
Description
|
Rating
|
NOTES
|
|
Nominal Input Voltage
|
120 VAC, 50-60Hz
|
NEC power Standards
|
|
MCOV (Maximum Continuous Operating Voltage)
|
175 VAC
|
|
|
Usable Voltage Range:
Wide Voltage Range (WVR) technology.
|
85-175 VAC
|
Fully dynamic performance with no fixed voltage clamping components offering superior performance when used with generators and in brown-out conditions
|
|
Input current rating
|
15, 20 or 30 Amps
|
Model dependent
|
|
Overload protection
|
|
Thermal circuit breakers where applicable
|
|
Noise, Suppression circuits
|
Series connected transformer in hot leg, followed by dynamic filtering.
|
Surge voltage totally canceled for optimum protection.
|
|
Mode of Operation:
(Avoid mode 2 and all-mode products to avoid system noise and reliability problems)
|
Mode 1 (Line-Neutral)
|
This mode protects L-N while avoiding system noise and product degradation associated with ground system contamination.
|
|
Endurance (ANSI C62.41 Standard surge)
|
1,000 surges- 6,000 Volt 3,000 Amp endurance rating
|
Filter technology does not degrade with use.
No sacrificial components.
|
|
EMI/RFI Filtering
|
20 dB rejection at 100 kHz.
|
|
|
Surge Voltage Let-Through* (ANSI 6,000V, 3,000A surge)
|
Less than 20 Volts peak.
|
The cancellation circuit effectively eliminates any surge damage potential.
|
|
Safety Agency Approvals
|
CSA 22.2 No. 8-M1986, UL 1283 5th edition, UL 1363
|
US and Canada Safety Certified.
|
|
Packaging
|
Heavy gauge steel cabinet
|
|
|
Outlets
|
2-10
|
Model dependent
|
|
Power cord, plug
|
6 ft nominal
|
Model dependent
|
|
Dimensions
|
|
Model dependent
|
|
Weight
|
7 lb. to 15 lb.
|
Model dependent
|
|
Warranty
|
10 years
|
|
*Surge Voltage Let-Through is the peak voltage that exceeds the powerline peak voltage.
|